Cleans heavily soiled systems

Reduces system malfunctions

Protects and enhances
the lifetime of the HVAC-system

TTM FiltrX® C450

Large system filter that removes magnetite

TTM FiltrX® C450 system filters effectively remove magnetite and dirt in heating or cooling systems. The system filter prevents magnetite and dirt from clogging or wearing down components in pumps, valves and other equipment, which otherwise risk seizing and leaking prematurely, even if they are turned off.


TTM FiltrX® C450 processes a partial flow and does not affect the pressure or flow in the system. As standard, the.

 

TTM FiltrX® C450 comes with a filter bag with a mesh size of 1 micron. Other types of filter bags are available on request.


Installation benefits:

  • Easy to install and commission
  • Can be installed for permanent or temporary
    operation
  • Can be installed in both small and large systems.
  •  

Operational benefits:

  • Robust design
  • Reduces operating costs
  • Reduces downtime
  • Extends HVAC-system lifetime.
  •  

Art. no. 519201

Installation

Also be aware that the magnet may interfere with electronic equipment and pacemakers.

Installation

TTM FiltrX® is connected with TTM Connection hoses on the system’s return conduit. Two bifurcations with ball valves with minimum dimensions DN20 and a spacing of at least 500 mm are installed on the bottom side of the conduit. The connections on the TTM MAG 250 are DN25 internal thread.

 

  • Connect a TTM Connection hose (1) from the first bifurcation to the pump (inflow from the system).
  • Connect a TTM Connection hose (2) from the second bifurcation to the filter holder (return to the system).
  • Open both ball valves (3) and wait until all the air in the filter holder has been evacuated through the top filter (4).
  • Start the pump.
  • Inspect the filter regularly and replace as needed. The interval depends on the size of the system and the quantity of particles in the fluid. We recommend that an inspection be held as early as after a few days in the event of heavily dirtied systems.
Description Specification
Art.no.: 519201
System pressure standard, total pressure at the connection point, max. 10 bar
Width x Length x Height (mm) 400 x 450 x 1060
Medium temperature 0 – + 60 ° C
Pressure class PN 10
Permissible liquids Water, glycol, alcohol, demineralized water
Connection dimension DN25, int. thread
External fuse 10 A
Magnetic insert Ø25 x 200mm
Mangetic strength 12000GS
Power rating 1 ~ 230 V, 50 Hz
Rated current 0,51 kW
Power 1 ~ 230V, 50Hz, plug
Voltage 2.34 A
Protection class IP44
Weight 33 kg
filtrx
Slide

Filter bad equipped with lifting handle for easy replacement. The bag filter is available in mesh sizes of 1 microns.

Slide

TTM Connection hose

The TTM Connection hose is a Butyl hose with stainless steel braiding and internally-threaded connections classified for pressures up to 10 bar.

Slide

Versatile transport trolley that simplifies transportation of TTM FiltrX® System filters.

Slide

Simonsland in Borås

When Kanico created a new district in the town of Borås, they chose TTM to supply shunt units for the HVAC systems. The area is called Simonsland and contains 60,000 m2 of buildings.

Slide

TTM Energiprodukter was one of the suppliers in the construction of the prestigious Copenhagen Opera House Together with their reseller, the company succeeded in winning the deal and delivering 98 different shunt units.

Slide

NCC are building their new head office at Järva Krog in Solna. The new head office has a strategic and easily accessible position adjacent to the E4 motorway.