Rotatable design
Pre-dimensioned and space-saving
Only one article number is required!
Home » Shunt-units » All-in-one shunts ready for delivery » Shuntomatic
Standardized shunt units for cooling or heating
TTM SHUNTOMATIC® is a pre-dimensioned plug-and-play shunt unit for heating or cooling systems. TTM SHUNTOMATIC® is equipped with a pressure-independent control valve (PICV), which always provides the correct control, even if the system pressure changes.
Advantages:
- Pre-dimensioned
- Easy to select via the ordering guide
- Dynamic control valve 100% valve authority
- Complete with a pump, control valve and actuator
- Few varieties, easy to select correct shunt unit
- Each shunt unit can be selected with or without communication pump
- Rotatable design
- Available in stock, short time delivery.
Design:
- 5 sizes for heating with heat insulation
- 5 sizes for cooling and cooling insulation
- Correctly rated pump
- Dynamic control valve (PICV)
- Actuator 24V 0-10 V control signal
- Selectable pump prepared for start, stop and alarm
TTM Shuntomatic® is environmentally assessed.
Shuntomatic® program:
Read more about:
Documentation:
Connection DN | 15 LF | 15 HF | 25 | 32 | 50 |
---|---|---|---|---|---|
A | 480 | 480 | 480 | 750 | 845 |
B | 340 | 340 | 340 | 485 | 610 |
C | 180 + pump | 180 + pump | 180 + pump | 285 + pump | 305 + pump |
D | 120 | 120 | 120 | 200 | 225 |
E | 120 | 120 | 120 | 200 | 240 |
F | 120 | 120 | 120 | 200 | 225 |
G | 67,5 | 67,5 | 67,5 | 67,5 | 70 |
H | 182 | 182 | 182 | 182 | 210 |
I | <173 | <175 | <193 | <200 | <205 |
J | 800 + pump | 800 + pump | 800 + pump | 800 + pump | 1050 + pump |
K | 93 | 93 | 93 | 93 | 112 |
Whight, appr. kg | 28 | 30 | 35 | 50 | 60 |
Max. pressure: 1.0 MPa and temperature range: +5 – +110 °C.
Dimensions refer to the standard version.
Some variations may occur with other equipment. All dimensions are in mm.
Shunt unit Heating | Connection internal (mm) | Flow range | Min. avail. pressure (kPa) | Max. loading pressure drop sec (kPa) | Max. effect (kW) at ΔT 30°C | Pump option | Effect (W) | Rate current (A) | Voltage (V) | Art.no. | ||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
l/s | l/h | |||||||||||||||
min | max | min | max | min | max | min | max | min | max | |||||||
Shuntomatic® V | DN15LF | 0.008 | 0.056 | 30 | 200 | 15.0 | 16.0 | 52 | 45 | 1.0 | 7.0 | Standard | 40 | 0.4 | 1×230 | 516699 |
Communication* | 100 | 1 | 1×230 | 516705 | ||||||||||||
Shuntomatic® V | DN15HF | 0.028 | 0.160 | 100 | 575 | 15.0 | 19.5 | 52 | 43 | 3.5 | 20 | Standard | 40 | 0.4 | 1×230 | 517023 |
Communication* | 100 | 1 | 1×230 | 516712 | ||||||||||||
Shuntomatic® V | DN25 | 0.078 | 0.347 | 280 | 1250 | 15.5 | 25.5 | 52 | 36 | 10 | 44 | Standard | 40 | 0.4 | 1×230 | 516729 |
Communication* | 100 | 1 | 1×230 | 516736 | ||||||||||||
Shuntomatic® V | DN32 | 0.222 | 0.986 | 800 | 3550 | 18.5 | 29.5 | 68 | 55 | 28 | 124 | Standard | 40 | 0.4 | 1×230 | 516941 |
Communication* | 100 | 1 | 1×230 | 516958 | ||||||||||||
Shuntomatic® V | DN50 | 0.625 | 2.639 | 2250 | 9500 | 10.5 | 29.5 | 110 | 42 | 78 | 331 | Standard | 40 | 1.3 | 1×230 | 516965 |
Communication* | 100 | 1.3 | 1×230 | 516972 |
Shunt unit Cooling | Connection internal (mm) | Flow range | Min. avail. pressure (kPa) | Max. loading pressure drop sec (kPa) | Max. effect (kW) at ΔT 5°C | Pump option | Effect (W) | Rate current (A) | Voltage (V) | Art.no. | ||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
l/s | l/h | |||||||||||||||
min | max | min | max | min | max | min | max | min | max | |||||||
Shuntomatic® K | DN15LF | 0.008 | 0.056 | 30 | 200 | 15.0 | 16.0 | 52 | 45 | 0.2 | 1.2 | Standard | 40 | 0.4 | 1×230 | 516743 |
Communication* | 100 | 1 | 1×230 | 516750 | ||||||||||||
Shuntomatic® K | DN15HF | 0.028 | 0.160 | 100 | 575 | 15.0 | 19.5 | 52 | 43 | 0.6 | 3.3 | Standard | 40 | 0.4 | 1×230 | 516767 |
Communication* | 100 | 1 | 1×230 | 516774 | ||||||||||||
Shuntomatic® K | DN25 | 0.078 | 0.347 | 280 | 1250 | 15.5 | 25.5 | 52 | 35 | 1.6 | 7.3 | Standard | 40 | 0.4 | 1×230 | 516781 |
Communication* | 100 | 1 | 1×230 | 516798 | ||||||||||||
Shuntomatic® K | DN32 | 0.222 | 0.986 | 800 | 3550 | 18.5 | 29.5 | 68 | 54 | 4.6 | 21 | Standard | 40 | 0.4 | 1×230 | 516989 |
Communication* | 100 | 1 | 1×230 | 516996 | ||||||||||||
Shuntomatic® K | DN50 | 0.625 | 2.639 | 2250 | 9500 | 10.5 | 29.5 | 110 | 41 | 13 | 55 | Standard | 40 | 1.3 | 1×230 | 517009 |
Communication* | 100 | 1.3 | 1×230 | 517016 |
TTM Shuntomatic® is dimensioned for fresh water.
*) Prepared for start, stop and alarm. DN32 and DN50 also have operation indication.
Robust floor stands with small foot-print made of epoxy-coated RHS tubes 50 × 30 mm.
Simonsland in Borås
When Kanico created a new district in the town of Borås, they chose TTM to supply shunt units for the HVAC systems. The area is called Simonsland and contains 60,000 m2 of buildings.
TTM Energiprodukter was one of the suppliers in the construction of the prestigious Copenhagen Opera House Together with their reseller, the company succeeded in winning the deal and delivering 98 different shunt units.
NCC are building their new head office at Järva Krog in Solna. The new head office has a strategic and easily accessible position adjacent to the E4 motorway.