Space saving design
System divider with heat exchanger
Flexible shunt unit for heating or cooling
Combined shunt units
TTM Shuntopac® 20-200 KV / KV Bypass is a combined shunt unit for both cooling and heating to a ventilation system.
The cooling heat exchanger is used to transfer both cooling and heating to the ventilation air. The traditional heat exchanger is removed as heat is transferred via a plate exchanger in the shunt unit’s secondary circuit.
TTM Shuntopac® 20-200 KV/KV Bypass is supplied with a fire and corrosion-proof housing in aluzinc sheet. Standard insulation is AF/Armaflex AF-2.
The shunt unit is environmentally approved.
Equipment TTM Shuntopac® KV
1. Control valve
2 pcs seat valves in a choice of make and type.
2. Adjustment valves
3 pcs in a choice of make. Make: TA STAD/F supplied as standard. Installed on pipe package with conical coupling or flange. Can also be supplied with dynamic adjustment valves, flow regulators or differential pressure regulator.
3. Shut-off valves
3 pcs ball valve DN 20-50 with full throughflow and extended stem or 3 pcs butterfly valve DN 65-200. Designed to act as end valves if the shunt unit is removed from the system. Installed on pipe package with conical coupling or flange.
4. Pump
Choice of make and type with “wet” or “dry” motor.
5. Plate heat exchanger
Welded, choice of make and type. Make: Swep supplied as standard. The heat exchanger is positioned on the front of the unit group to facilitate service. Other positioning is available on request, provided the heat exchanger’s size and configuration permits it.
6. Non-return valve
1 pc with sprung disc. Drain plug with hose screw
connection.
7. Thermometers
6 pcs, graduated -40 – +40 °C or 0-120 °C.
8. Vacuum and safety valve
Equipment TTM Shuntopac® KV Bypass
1. Control valve
2 pcs seat valves in a choice of make and type.
2. Adjustment valves
3 pcs in a choice of make. Make: TA STAD/F supplied as standard. Installed on pipe package with conical coupling or flange. Can also be supplied with dynamic adjustment valves, flow regulators or differential pressure regulator.
3. Shut-off valves
3 pcs ball valve DN 20-50 with full throughflow and extended stem or 3 pcs butterfly valve DN 65-200. Designed to act as end valves if the shunt unit is removed from the system. Installed on pipe package with conical coupling or flange.
4. Pump
Choice of make and type with “wet” or “dry” motor.
5. Plate heat exchanger
Welded, choice of make and type. Make: Swep supplied as standard. The heat exchanger is positioned on the front of the unit group to facilitate service. Other positioning is available on request, provided the heat exchanger’s size and configuration permits it.
6. Non-return valve
1 pc with sprung disc. Drain plug with hose screw
connection.
7. Thermometers
6 pcs, graduated -40 – +40 °C or 0-120 °C.
8. Vacuum and safety valve
Dimensions TTM Shuntopac® 20-200 KV / KV Bypass DN20-50
Connection DN | 20 | 25 | 32 | 40 | 50 |
---|---|---|---|---|---|
A1 | 1200 | 1170 | 1170 | 1170 | 1230 |
A2 | 800 | 1285 | 1285 | 1285 | 1330 |
B | 745 | 745 | 745 | 745 | 745 |
C | 200 | 200 | 200 | 200 | 215 |
C2 | 315 | 315 | 315 | 315 | 315 |
D | 85 | 85 | 85 | 85 | 85 |
E | Variable | Variable | Variable | Variable | Variable |
F | 315 | 315 | 315 | 315 | 315 |
G | 930 | 930 | 930 | 930 | 930 |
H | 100 | 100 | 100 | 100 | 100 |
I | 285 | 285 | 285 | 285 | 285 |
J | 600 | 600 | 600 | 600 | 675 |
J2 | 715 | 715 | 715 | 715 | 755 |
K | Variable | Variable | Variable | Variable | Variable |
Weight, approx. kg | 90 | 95 | 100 | 110 | 180 |
Dimensions TTM Shuntopac® 20-200 KV / KV Bypass DN65-100
Connection DN | 65 | 80 | 100 |
---|---|---|---|
A1 | 1760 | 1760 | 2110 |
A1 | 1760 | 1760 | 2110 |
B | 1860 | 1910 | 2260 |
C | 300 | 300 | 350 | C2 | 400 | 450 | 500 |
D | 130 | 130 | 180 |
E | variabel | variabel | variabel |
F | 295 | 295 | 395 |
G | 995 | 1000 | 1240 |
H | 140 | 140 | 140 |
I | 285 | 285 | 355 |
J | 1190 | 1190 | 1400 | J2 | 1290 | 1340 | 1550 |
K | Variable | Variable | Variable |
Weight, approx. kg | 260 | 340 | 480 |
TTM Shuntopac® 20-200 KV / KV Bypass
Configuration
Both the heating primary side and cooling media side can be supplied with a choice of shunt connection. The heat exchanger is installed on the front of the shunt unit to facilitate service.
Example of Shuntopac with combined heating and cooling function.
Customised design
- Pipe package in choice of material, e.g. stainless steel, copper etc.
-
Anti-corrosive painted pipe mixing loop, e.g. epoxy enamelled.
Contact TTM to discuss your requirements.
TTM SHUNTOPAC® Green Line is a category of shunt units equipped with low-lead valves. Green Line is intended for customers with high demands for improved environmental assessments
TTM SHUNTOPAC® Dynamic gives correct regulation even in systems with varying differential pressures or where the differential pressure is unknown.
TTM SHUNTOPAC® EM is a category of shunt units equipped with ultrasound energy metering equipment according to EN 1434 class 2 and MID 2004/22/EC.
Robust floor stands with small foot-print made of epoxy-coated RHS tubes 50 × 30 mm.